I. Structural Features and Applications
Structural Features
- Fire Groove Connection End groove dimensions comply with GB 5135.11-2019 "Automatic Sprinkler Fire Suppression Systems Part 11: Grooved Pipe Fittings". They are compatible with fire-specific grooved clamps (including nitrile rubber seals). Installation requires no flange bolts and can be completed within 3 minutes, meeting the rapid construction needs of fire pipelines (in accordance with GB 50974-2014 "Technical Specifications for Fire Water Supply and Fire Hydrant Systems", clause 8.2.9).
- Hard Seal Fire Adaptor The sealing surface between the gate and valve body adopts 13Cr stainless steel hard seal overlay welding (Sealing surface hardness ≥HRC55), resistant to the scouring of sand, rust, and other particles contained in fire water, leakage rate ≤0.05% × rated flow (according to GB/T 13927-2008 Fire Valve Testing Standard), ensuring no medium leakage during a fire.
- Stem Space Optimization The valve stem is built-in and not exposed. The overall height is 20% lower than that of the same diameter open stem valve, suitable for small spaces such as fire pipe wells and ceilings. It prevents the valve stem from being corroded by fire water or deformed by external forces, and complies with the compactness requirements for fire valves in GB 5135.6-2018.
- Fire Prevention and Corrosion Treatment The valve body uses ductile iron QT450-10 (compliant with GB/T 1348-2009). The surface is epoxy resin sprayed (thickness ≥150μm), resistant to long-term immersion corrosion by fire water; the valve stem uses 2Cr13 stainless steel (surface chrome-plated), salt spray test ≥1000 hours, ensuring long-term flexible opening and closing.
Applications
II. Main Technical Parameters (According to National Standard Conventional Values)
III. Main Component Materials (Conventional Configuration)
IV. Main External Shape and Connection Dimensions (Unit: mm, According to National Standard Conventional Values)
V. Application scenarios
- Automatic water spray fire extinguishing system :Branch pipes of sprinkler system zoning, front/rear of signal valve. Groove connection adapts to quick installation of pipelines inside the ceiling, hard seal is resistant to the scouring of impurities during pipeline flushing (conforms to GB 50084-2017 Article 6.2.7).
- Fire hydrant system :Main pipes of fire hydrant network, branch pipes of pump connectors. Concealed rod design saves space in pipe shafts, red handwheel facilitates identification during fire inspection (conforms to GB 50974-2014 Article 8.3.1).
- Fire water pump room :Water pump outlet pipe, pressure stabilizing pump inlet and outlet pipes. Hard seal adapts to pressure fluctuations during pump start and stop, groove connection shortens the installation time of pipelines in the pump room (adapts to fire pump room construction specifications).
- Industrial fire protection network :Branch pipes of factory fire protection (such as paint spraying workshops, warehouses). Anti-corrosion treatment is resistant to industrial environments, ensuring reliable on/off during a fire.
Keyword
Groove hard seal hidden stem gate valve
The grooved hard-sealed gate valve is a special valve manufactured by our company in accordance with national fire protection standards. Core advantages: grooved connection meets the requirements of rapid fire protection construction, hard sealing is resistant to impurity erosion, hidden stem saves space, and fire protection grade anti-corrosion is durable. It conforms to standards such as GB 5135.6 and GB 50974, is adaptable to PN16, DN50~200, is specially designed for fire protection water systems, and is a reliable on-off device for fire protection pipe networks such as automatic sprinkler fire extinguishing systems and fire hydrant systems, meeting the needs of fire protection acceptance and daily safe operation.