ZSXF-Z fire signal gate valve
+
  • ZSXF-Z fire signal gate valve

I. Structural Features and Applications

Structural Features

  • Fire Signal Feedback :Built-in mechanical linkage signaling device (microswitch + gear transmission). When the valve closes to an opening ≤75% (i.e., more than 25% closed), it automatically outputs a passive dry contact signal (DC24V/3A), which can be directly connected to the fire control room host for real-time feedback of the valve status. This complies with the requirements for signal valves in GB 5135.6-2018 "Automatic Sprinkler Fire Suppression Systems Part 6: General Valves"; the signal box has an IP54 protection rating (dust and splash proof), suitable for the humid environment of fire pipelines.
  • Elastic Seat Seal :The gate plate is completely covered with EPDM rubber (compliant with GB/T 21873-2008), which elastically fits the sealing surface of the valve body. It seals by self-tightening through medium pressure, with a bidirectional sealing leakage rate ≤0.01% (tested according to GB/T 13927-2008), ensuring no leakage of fire water and suitable for media such as clear water and fire foam.
  • Concealed Stem Structure Design :The valve stem is built-in, and does not rise and fall externally during opening and closing. The overall height is fixed (15% lower than the same diameter exposed stem valve), suitable for scenarios with limited space in fire pipelines such as pipe wells and ceilings. This complies with the structural requirements for fire gate valves in GB/T 12232-2005.
  • Fire-Specific Connection :The flange connection complies with GB 9113-2010 (with water stop ring), and the bolt hole spacing tolerance is ±0.2mm, ensuring precise docking with the fire pipeline; the valve body surface is epoxy resin coated (thickness ≥150μm), resistant to fire water corrosion, and complies with the corrosion protection requirements for valves in GB 50974-2014 "Technical Specifications for Fire Water Supply and Fire Hydrant Systems".

Applications

Specifically designed for fire systems, used for on/off control of pipelines in automatic sprinkler fire suppression systems, fire hydrant systems, and fire pump rooms, while providing real-time feedback on the valve status to prevent unauthorized closure or misoperation leading to interruption of fire water supply. Suitable for fire pipeline networks in various buildings such as shopping malls, residential buildings, and factories. It is a key valve for "on/off + status monitoring" in fire systems.
 

II. Main Technical Parameters (According to National Standard Conventional Values)

Item Parameter Range
Nominal Pressure (PN) PN16 (1.6MPa, commonly used pressure level for fire systems)
Shell Test Pressure 2.4MPa (1.5 times the nominal pressure, according to GB/T 13927-2008)
Sealing Test Pressure 1.76MPa (1.1 times the nominal pressure, according to GB/T 13927-2008)
Applicable Medium Clear water, fire foam (concentration ≤3%), neutral fire water
Applicable Temperature (°C) 0~80 (conventional temperature range for fire water, EPDM rubber adaptable)
Nominal Diameter (DN) DN50~300 (conventional diameter for fire pipelines, DN300 and above can be customized)
Signal Characteristics Passive dry contact, contact capacity DC24V/3A, signal triggering accuracy ±5% (closing 25%±1.25% trigger)
Implementation Standards GB 5135.6-2018 "Automatic Sprinkler Fire Suppression Systems Part 6: General Valves", GB 50974-2014, GB/T 12232-2005

 

III. Main Component Materials (Conventional Configuration)

Product Part Material (National Standard Conventional Material)
Valve Body / Valve Cover Ductile iron QT450-10 (compliant with GB/T 1348-2009, inner wall epoxy resin coated)
Gate Plate Ductile iron + EPDM rubber (overall vulcanization, rubber compliant with GB/T 21873-2008)
Valve Stem 2Cr13 stainless steel (tempering treatment, chrome-plated surface for corrosion protection, compliant with GB/T 1220-2007)
Signaling Device Housing: Aluminum alloy (surface spray-painted for corrosion protection); Internal: Microswitch (silver contact), steel gear
Sealing Element EPDM rubber (water-resistant, fire foam resistant, aging life ≥10 years)
Flange Sealing Surface Ductile iron (with water line, with rubber gasket, compliant with GB 9113-2010)
Bolts / Nuts Zinc-plated carbon steel (Grade 8.8, compliant with GB/T 3098.1-2010, for fire pipelines)
Handwheel Cast iron (surface spray-painted, with "Open/Close" fire marking, red warning paint)

 

IV. Main External Dimensions and Connections (Unit: mm, according to national standard conventional values)

Nominal Diameter DN

Flange Outer Diameter D

Bolt Hole Center Circle

Diameter D1

Bolt Hole Diameter d

Number of Bolts n

Structural Length L

(GB 5135.6)

Total Height H

(Including Signaling Device)

Handwheel Diameter D0

Signal Box Dimensions

(Length × Width × Height)

50

165

125

18

4

178

360

180

100×80×60

65

185

145

18

4

190

400

200

100×80×60

80

200

160

18

8

203

440

200

120×90×70

100

220

180

18

8

229

490

240

120×90×70

150

285

240

22

8

267

610

320

140×100×80

200

340

295

22

12

292

730

400

140×100×80

250

405

355

26

12

330

850

480

160×110×90

300

460

410

26

16

356

980

560

160×110×90

 

V. Application Scenarios

  • Automatic Sprinkler Fire Suppression System : Installation of sprinkler system main pipes and branch pipes, real-time feedback of valve status, ensuring unobstructed pipelines during fire (compliant with GB 50084-2017 "Design Code for Automatic Sprinkler Fire Suppression Systems", Article 6.2.7).
  • Fire Hydrant System : Main pipes of fire hydrant network, branch pipes of pump connectors, preventing non-fire operations from closing valves, signal access to fire control room for linkage alarm (compliant with GB 50974-2014, Article 8.3.1).
  • Fire Water Pump Room : Water pump outlet pipe, pressure regulating pump inlet and outlet pipes, valve status linked with pump start and stop, shutdown over 25% triggers pump protection shutdown (adaptable to fire pump control standards).
  • Industrial Fire Network : Key nodes of factory workshop fire pipelines, adapting to the fire acceptance needs of small and medium-sized enterprises, signaling devices meet fire detection standards.

 

Keyword

ZSXF-Z fire signal gate valve
+
  • ZSXF-Z fire signal gate valve

ZSXF-Z fire signal gate valve

The ZSXF-Z fire signal gate valve is a fire-fighting valve produced by our factory according to national standards. Its core function is "on-off control + status feedback": When the valve is closed more than 25%, a passive signal is output through a mechanical linkage signal device, which is compatible with the fire control room monitoring; the elastic seat seal ensures zero leakage of fire water, the dark stem structure saves installation space, and the flange connection conforms to fire pipeline standards. The product covers PN16, DN50~300, and its materials and performance strictly comply with GB 5135.6, GB 50974 and other standards. It is suitable for various building fire protection systems and is a reliable guarantee for the safe operation of the fire pipeline network, meeting the needs of regular production and market supply of valve manufacturers.

Professional valve manufacturing 



Get a Quote

Note: Please leave your contact information, and our professionals will contact you as soon as possible!

Submit message