Gaote Holding Group focuses on the research and development and production of various valves
-
Products
-
-
-
I. Structural Features and Applications
Structural Features
- Indicating Scale Design Equipped with a mechanical pointer scale (0-100% opening scale), which synchronously displays the actual valve opening through gear transmission. The pointer accuracy is ±2.5%, facilitating intuitive judgment of the status during fire inspection; the scale housing is made of transparent polycarbonate (scratch and waterproof), suitable for humid fire environments, and meets the requirements of GB 50974-2014 for visible valve status.
- Groove Quick Connection End groove dimensions comply with GB 5135.11-2019 (groove width 11.9mm, groove depth 3.2mm), suitable for fire-专用卡箍 (including nitrile rubber sealing gasket). Installation requires no flange bolts, resulting in 30% higher construction efficiency than flange connections and meeting the demand for rapid fire pipeline installation.
- Elastic Seat Seal The gate plate is completely covered with EPDM rubber (compliant with GB/T 21873-2008), which elastically fits the sealing surface of the valve body. The bidirectional sealing leakage rate ≤0.01% (tested according to GB/T 13927-2008) ensures that there is no leakage of fire water and is suitable for clean fire water media.
- Fire protection coating The valve body is made of ductile iron QT450-10 (epoxy powder coating ≥150μm on the inner wall, fire-red coating on the outer wall), and the valve stem is made of 2Cr13 stainless steel (chromium-plated corrosion protection), which is resistant to long-term immersion in fire water and meets the corrosion resistance requirements of fire valves in GB 5135.6-2018.
Applications
II. Main Technical Parameters (According to National Standard Conventional Values)
| Item | Parameter Range |
|---|---|
| Nominal Pressure (PN) | PN16 (1.6MPa, commonly used in fire systems) |
| Shell Test Pressure | 2.4MPa (1.5 times the nominal pressure) |
| Sealing Test Pressure | 1.76MPa (1.1 times the nominal pressure) |
| Applicable Medium | Clean fire water (without obvious particles) |
| Applicable Temperature (°C) | 0~80 (EPDM rubber adaptable) |
| Nominal Diameter (DN) | DN50~200 (conventional diameter of fire groove) |
| Scale Accuracy | ±2.5% (full open to full close stroke) |
| Implementation Standards | GB 5135.6-2018, GB 50974-2014, GB/T 12232-2005 |
III. Main Component Materials (Conventional Configuration)
| Product Part | Material (National Standard Conventional Material) |
|---|---|
| Valve Body / Valve Cover | Ductile iron QT450-10 (inner wall epoxy powder coating, outer wall fire-red coating) |
| Gate Plate | Ductile iron + EPDM rubber (overall wrapping, compliant with GB/T 21873) |
| Valve Stem | 2Cr13 stainless steel (quenched and chrome-plated, resistant to fire water corrosion) |
| Scale Component | Polycarbonate housing + steel pointer + copper gear (scratch and waterproof) |
| Groove End | Integrated casting with the valve body (compliant with GB 5135.11-2019) |
| Sealing Element | Nitrile rubber NBR (groove sealing), EPDM rubber (gate plate sealing) |
| Handwheel | Cast iron (red spray paint, with "Fire Protection" marking) |
IV. Main External Shape and Connection Dimensions (Unit: mm, According to National Standard Conventional Values)
Nominal Diameter DN |
Groove Outer Diameter Dg |
Groove Width C |
Structural Length L |
Total Height H (Including scale) |
Scale Dimensions (Length × Width) |
Handwheel Diameter D0 |
Adaptable Clamp Specifications |
|---|---|---|---|---|---|---|---|
| 50 | 60.3 | 11.9 | 178 | 360 | 100×80 | 180 | DN50 |
| 100 | 114.3 | 11.9 | 229 | 490 | 120×90 | 240 | DN100 |
| 150 | 168.3 | 11.9 | 267 | 610 | 140×100 | 320 | DN150 |
| 200 | 219.1 | 11.9 | 292 | 730 | 160×110 | 400 | DN200 |
V. Application Scenarios
- Automatic Sprinkler System Sprinkler main pipe, zone control valve. The scale facilitates precise flow control during commissioning (compliant with GB 50084-2017).
- Fire Hydrant System Main pipe, water pump connector branch pipe, visually displays whether the valve is normally open, facilitating inspection (compliant with GB 50974-2014).
- Fire water pump room Water pump outlet pipe, scale assists in confirming valve opening and linkage status with the water pump, avoiding misoperation.
Keyword
Fire RVGK grooved apparent valve (ZK85X)
Professional valve manufacturing
Contact Us
Belongs to:
Gaote Holding Group Co., Ltd.
Tel: +8613400888017
Email: gaotegroup@126.com
Address: Chenggong Development Zone, Ximei Street, Nan'an City, Quanzhou City, Fujian Province
Leave a message
* Note: Please be sure to fill in the information accurately and keep the communication open.
COOKIES
Our website uses cookies and similar technologies to personalize the advertising shown to you and to help you get the best experience on our website. For more information, see our Privacy & Cookie Policy
COOKIES
Our website uses cookies and similar technologies to personalize the advertising shown to you and to help you get the best experience on our website. For more information, see our Privacy & Cookie Policy
These cookies are necessary for basic functions such as payment. Standard cookies cannot be turned off and do not store any of your information.
These cookies collect information, such as how many people are using our site or which pages are popular, to help us improve the customer experience. Turning these cookies off will mean we can't collect information to improve your experience.
These cookies enable the website to provide enhanced functionality and personalization. They may be set by us or by third-party providers whose services we have added to our pages. If you do not allow these cookies, some or all of these services may not function properly.
These cookies help us understand what you are interested in so that we can show you relevant advertising on other websites. Turning these cookies off will mean we are unable to show you any personalized advertising.