I. Structural Features and Applications
Structural Features
- Visible Stem Opening The stem rises and falls synchronously with the gate and is fully exposed. The valve opening can be intuitively judged by the length of the stem extension (fully open/fully closed status is clearly visible). This facilitates fire inspection and condition confirmation, meeting the requirements of GB 50974-2014 "Technical Specifications for Fire Water Supply and Fire Hydrant Systems" for monitoring the valve status; the stem uses trapezoidal threads (pitch 3~6mm), providing stable opening and closing torque and easy manual operation.
- Groove Quick Connection The groove dimensions at the end meet GB 5135.11-2019 "Automatic Sprinkler Fire Suppression Systems Part 11: Grooved Pipe Fittings". It is compatible with fire-specific grooved clamps (including nitrile rubber seals). Installation does not require flange bolts, and pipe connection can be completed within 10 minutes. The construction efficiency is 40% higher than that of flange connection, meeting the emergency installation needs of fire pipelines.
- Elastic Seat Seal The gate is completely covered with EPDM rubber (compliant with GB/T 21873-2008), forming an elastic fit with the valve body sealing surface. Self-tightening sealing is achieved through fire water pressure. The bidirectional sealing leakage rate ≤0.01% (according to GB/T 13927-2008 Fire Valve Testing Standard) ensures no medium leakage during a fire and is suitable for clean fire water media.
- Fire-Specific Design The valve body is made of ductile iron QT450-10 (compliant with GB/T 1348-2009). The surface is sprayed with fire-red epoxy coating (thickness ≥150μm), resistant to long-term immersion corrosion by fire water; the handwheel is painted red and marked with "Fire-Specific" identification for quick identification in emergencies, meeting the identification requirements of GB 5135.6-2018 for fire valves.
Applications
II. Main Technical Parameters (According to National Standard Conventional Values)
III. Main Component Materials (Conventional Configuration)
IV. Main External Dimensions and Connections (Unit: mm, According to National Standard Conventional Values)
V. Application Scenarios
- Automatic water spray fire extinguishing system :Main pipe of sprinkler system, front end of zone control valve. The exposed stem design facilitates inspection and confirmation of the "normally open" status. The grooved connection is suitable for quick installation of pipes inside the ceiling (compliant with GB 50084-2017, Article 6.2.7).
- Fire hydrant system :Main pipe of fire hydrant network, community fire loop network. The red handwheel facilitates quick identification in emergencies, and the exposed stem opening allows for intuitive judgment of whether the valve is normally open (compliant with GB 50974-2014, Article 8.3.1).
- Fire pump room :Water pump suction pipe, discharge pipe. Grooved connection shortens the installation time of pipes in the pump room, and the exposed stem design facilitates confirmation of the valve status in conjunction with the water pump (adaptable to fire pump room construction specifications).
- High-rise residential fire pipe network :Branch pipes of fire risers inside the pipe shaft. Grooved connection reduces the space occupied by the pipe shaft, and the exposed stem facilitates daily inspection and maintenance by the property management.
Keyword
Fire fighting RRGX trench-type gate valve (Z81X)
The Fire RRGX grooved-type rising stem gate valve (Z81X) is a specialized gate valve manufactured by our company in accordance with national fire protection standards. Key advantages include: visible stem design for easy inspection, grooved connection for quick installation, elastic seat seal to ensure zero leakage of fire water, and red fire protection markings in compliance with regulations. It conforms to GB 5135.6, GB 50974, and other standards, is suitable for PN16, DN50~200, and is specifically designed for fire water systems. It is a reliable on/off device for fire protection networks such as automatic sprinkler systems and fire hydrant systems, meeting the requirements of fire acceptance and daily safe operation.
Professional valve manufacturing
Contact Us
Belongs to: