I. Core Structural Features

The core structure of the AX742X diaphragm safety pressure relief valve conforms to   GB/T 12238 (General valves, flange and double-clamp connection valve structural length), GB/T 13927 (Industrial valves, pressure test) and other national standards, the key structures are as follows:
  1. Sealing and Connection :Using Diaphragm soft seal (Nitrile rubber diaphragm), when closed, the sealing performance meets the sealing test requirements of GB/T 13927, ensuring zero leakage of the medium; the main body is Flange connection (Conforms to GB/T 9119 national standard), convenient installation for adapting to pipeline systems.
  2. Pressure relief and pressure control :Through Hydraulic drive + pressure guiding tube linkage Realize dual functions: ① Pressure relief function: When the medium pressure exceeds the limit, the diaphragm assembly automatically opens to relieve pressure; ② Pressure holding function: When the pressure drops to the set value, it automatically closes to maintain stable system pressure (conforms to GB/T 12244 performance requirements for pressure relief/pressure holding valves); the top brass adjusting screw supports Manual calibration of pressure threshold , adapting to different working conditions.
  3. Monitoring and filtration :A single-sided pressure gauge (brass material) monitors the medium pressure in real time to ensure precise control; the valve body is built-in Stainless steel filter component (Adaptable to ≤1.2mm impurities in the medium), protecting the diaphragm and adjusting components from blockage and extending the life of the valve group.
  4. Pressure guiding transmission :The phosphor bronze pressure guiding tube connects the valve body and the control component, accurately transmitting the medium pressure signal to ensure the speed of pressure relief/pressure holding response.

 

II. Main Technical Parameters (National Standard)

Parameter Name Value/Range Unit National Standard Basis
Nominal pressure (PN) PN16 MPa GB/T 1048
Nominal diameter (DN) DN50~DN300 mm GB/T 1047
Applicable medium Water, sewage and other fluids - Product design adaptation
Operating temperature 0℃~80℃ ℃ Seal temperature resistance adaptation
Shell test pressure 2.4 MPa MPa GB/T 13927
Sealing test pressure 1.76 MPa MPa GB/T 13927
Pressure relief pressure range 0.1~1.6 MPa MPa GB/T 12244
Filtration accuracy ≤1.2 mm mm Product design specifications

 

III. Main Part Materials (National Standard)

Part Name Material Implementation Standard
Valve body Ductile iron GB/T 1348-2019
Valve cover Ductile iron GB/T 1348-2019
Diaphragm Nitrile rubber GB/T 21873-2008
Pressure guiding tube Phosphor bronze GB/T 1527-2017
Pressure gauge Brass + Glass GB/T 1226-2019
Fasteners Stainless steel (304) GB/T 3098.6
Filter component Stainless steel (304) GB/T 20878-2007
Adjusting screw Brass GB/T 5231-2012

 

IV. Dimensions and Specifications (National Standard)

Specifications and Models

Nominal diameter DN (mm)

Flange outer diameter D

(mm)

Bolt hole center distance K

(mm)

Number of bolt holes n

(pcs)

Bolt diameter d

(mm)

Structural length L

(mm)

National Standard Basis

AX742X-16Q

50

165

125

4

18

230

GB/T 9119, GB/T 12221

AX742X-16Q

80

200

160

8

18

280

GB/T 9119, GB/T 12221

AX742X-16Q

100

220

180

8

18

320

GB/T 9119, GB/T 12221

AX742X-16Q

150

285

240

8

22

400

GB/T 9119, GB/T 12221

 

V. Typical Application Scenarios

AX742X diaphragm-type safety pressure relief and pressure maintaining valve is suitable for multiple fields Overpressure protection + pressure stabilization Requirements:
  • Water supply and drainage engineering City water supply mains, secondary pressure boosting pump stations, pressure relief to protect downstream pipelines and equipment, pressure maintenance to maintain system pressure stability;
  • Fire protection system Overpressure relief for fire protection networks, pressure maintenance to ensure sufficient water pressure during fire fighting, filtration of impurities to prevent valve group blockage;
  • Industrial circulating water Cooling water system pressure regulation, pressure relief to avoid equipment overpressure, pressure maintenance to ensure stable circulation flow;
  • Heating system Pressure relief for hot water circulation networks, pressure maintenance to maintain terminal heating pressure, filtration of impurities to protect temperature control components;
  • Building water supply High-rise residential/commercial building water supply systems, pressure relief to prevent pipe bursts, pressure maintenance to stabilize household water pressure.
 
Typical installation diagram  

 

Keyword

AX742X diaphragm safety relief pressure valve
+
  • AX742X diaphragm safety relief pressure valve

AX742X diaphragm safety relief pressure valve

The AX742X diaphragm safety pressure relief valve uses a flange connection and integrates four core functions: diaphragm soft sealing, pressure relief and pressure holding dual control, pressure monitoring, and impurity filtration. It conforms to national standards such as GB/T 12238 and GB/T 13927. It automatically responds to pressure changes through hydraulic drive, manually calibrates the pressure threshold, and the filter component ensures the cleanliness of the valve group. It features reliable sealing and precise control. It is widely used in water supply and drainage, fire protection, industrial circulating water, and other fields, providing double protection of overpressure protection + pressure stability for fluid systems.