YQ98005 filter piston double-check float valve
+
  • YQ98005 filter piston double-check float valve

I. Core Structural Features

The core structure of the YQ98005 filter piston dual-control float valve conforms to   GB/T 12238   and other national standards. Key structural features are as follows:
  1. Connection and Filtration :The valve body uses flange connection (in accordance with GB/T 9119 national standard), facilitating pipeline integration; built-in Y-type filter structure (Y-type flow path design in the valve body image), filtering impurities ≤1.2mm in the medium, ensuring valve cavity cleanliness, and conforming to the structural specifications for filter valves in GB/T 12238.
  2. Dual Control Drive :Uses electromagnetic + manual compound drive The top electromagnetic valve (with wiring terminals) receives electrical signals and transmits the medium pressure through a phosphor bronze pressure transmission tube to drive the piston assembly to automatically switch on and off; the single-sided red handwheel supports manual adjustment to meet emergency operation or debugging needs, conforming to the functional requirements of drive control in GB/T 12222.
  3. Sealing Form :The piston and valve seat use soft sealing structure (seal material compatible with the medium). When closed, the sealing performance meets the sealing test requirements of GB/T 13927, ensuring zero leakage of the medium.
  4. Float Linkage :Through the external float signal (requires a matching float device) to actuate the electromagnetic valve, realizing automatic water level replenishment control (conforming to the GB/T 18145 float valve national standard logic), requiring no continuous power supply, energy-efficient and reliable.
  5. Pressure Transmission :The phosphor bronze pressure transmission tube connects the valve body and control components, accurately transmitting the medium pressure signal to ensure control accuracy and response speed.

 

II. Main Technical Parameters (National Standard)

Parameter Name Value / Range Unit National Standard Basis
Nominal Pressure (PN) PN16 MPa GB/T 1048
Nominal Diameter (DN) DN40~DN200 mm GB/T 1047
Applicable Medium Water, sewage and other fluids - Product design adaptation
Operating Temperature 0℃~80℃ ℃ Seal temperature resistance adaptation
Shell Test Pressure 2.4 MPa MPa GB/T 13927
Sealing Test Pressure 1.76 MPa MPa GB/T 13927
Electromagnetic Valve Voltage AC220V/DC24V V GB/T 14048.4
Filtration Accuracy ≤1.2 mm mm Product design specifications
Float Control Range 0.02~0.6 MPa MPa GB/T 18145

 

III. Main Component Materials (National Standard)

Component Name Material Implementation Standard
Valve Body Ductile Iron GB/T 1348-2019
Valve Cover Ductile Iron GB/T 1348-2019
Piston Stainless Steel (304) GB/T 20878-2007
Seal Nitrile Rubber GB/T 21873-2008
Electromagnetic Valve Assembly Brass + Stainless Steel GB/T 5231-2012
Pressure Transmission Tube Phosphor Bronze GB/T 1527-2017
Handwheel Cast Iron GB/T 9439-2010
Fasteners Stainless Steel (304) GB/T 3098.6
Filter Component Stainless Steel (304) GB/T 20878-2007

 

IV. Dimensions and Specifications (National Standard)

Specifications and Models

Nominal Diameter DN

(mm)

Flange Outer Diameter D

(mm)

Bolt Hole Center Distance K

(mm)

Number of bolt holes n

(pcs)

Bolt diameter d

(mm)

Structure length L

(mm)

National Standard Basis

YQ98005-16Q

50

165

125

4

18

230

GB/T 9119、GB/T 12221

YQ98005-16Q

80

200

160

8

18

280

GB/T 9119、GB/T 12221

YQ98005-16Q

100

220

180

8

18

320

GB/T 9119、GB/T 12221

YQ98005-16Q

150

285

240

8

22

400

GB/T 9119、GB/T 12221

 

V. Typical Application Scenarios

YQ98005 filter piston dual-control float valve adaptable to multiple fields Automatic liquid level control + manual emergency Demand:
  • Water supply and drainage engineering :Automatic water replenishment for urban water supply tanks and reservoirs, float-linked solenoid valve for precise liquid level control, manual valve for emergency maintenance;
  • Fire fighting system :Fire water tank / pressure tank level control, solenoid valve automatic water replenishment, manual valve to ensure emergency condition flow regulation;
  • Building water supply :Water tank replenishment for high-rise residential buildings / commercial buildings, filtering impurities to prevent solenoid valve blockage, dual-control design to improve reliability;
  • Wastewater treatment :Wastewater regulating pool, clear water pool level control, Y-type filtration to cope with wastewater impurities, dual-control adaptation to complex working conditions;
  • Industrial circulating water :Cooling tower, circulating water tank replenishment system, float linkage to achieve unattended operation, manual valve to support equipment maintenance.
 

Keyword

YQ98005 filter piston double-check float valve
+
  • YQ98005 filter piston double-check float valve

YQ98005 filter piston double-check float valve

The YQ98005 filter piston dual-control float valve is developed by Gaote Holding Group and strictly follows national standards such as GB/T 12238 and GB/T 13927 in its design. It integrates four core functions: Y-type filtration, electromagnetic + manual dual control, piston drive, and float linkage. It uses flange connections to adapt to national standard pipelines. It can automatically respond to liquid level signals for water replenishment, manual emergency control, filter impurities to ensure valve group cleanliness, and features reliable sealing and precise control. It is widely used in water supply and drainage, fire protection, construction, and wastewater treatment, providing a dual insurance solution of automation + emergency protection for fluid systems.

Professional valve manufacturing 



Get a Quote

Note: Please leave your contact information, and our professionals will contact you as soon as possible!

Submit message